IEC 61850-9-2 Transformer Auxiliary Relay for Mechanical protection recorder 1024
The PCS-974 relay provides mechanical protection for transformer tanks. The source of mechanical protection can be designed from non-electrical quantities, such as gas, oil temperature, winding temperature, pressure and oil level. It receives the mechanical inputs from transformer tank and issues the tripping or alarm command with or without time delay. The mechanical inputs employ the inputs with large pickup power instead of common binary inputs.
Protection
and
Monitoring
Mechanical
protection
(26:
oil
and
winding
temperature;
63:
gas,
pressure;
71:
oil
level;
etc).
Self
diagnostic.
Auxiliary
power
supervision.
Event
recorder
including
1024
disturbance
records,
1024
binary
events,
1024
supervision
events
and
1024
operating
logs.
Communication
Two 10Base-T/100Base-TX (RJ45) ports and two optional 100Base-FX ports with IEC 61850-8-1 MMS and GOOSE
for non-time-critical message,
IEC 60870-5-103 over TCP/IP or DNP 3.0.
Two RS-485 rear ports with IEC 60870-5-103.
Six or Eight 100Base-FX ports with IEC 61850-9-2 Sampling Value and GOOSE for time-critical message.
One RS-485 rear port for clock synchronization.
One RS-232 rear port for printer.
1 faceplate RJ45 port for testing and setting.
Clock synchronization via Pulse-Per-Second,
IRIG-B and SNTP.