China Portable 3 Phase Portable Reference Standard For Single Phase Meter Calibration for sale
China Portable 3 Phase Portable Reference Standard For Single Phase Meter Calibration for sale
  1. China Portable 3 Phase Portable Reference Standard For Single Phase Meter Calibration for sale
  2. China Portable 3 Phase Portable Reference Standard For Single Phase Meter Calibration for sale

Portable 3 Phase Portable Reference Standard For Single Phase Meter Calibration

Price Negotiable
MOQ Negotiable
Delivery Time Negotiable
Brand GENY
Place of Origin CHINA
Certification ISO, CE
Model Number YC2000A
Payment Terms L/C, T/T, D/P
Supply Ability 300/Year

Product Details

Product Specification

Brand Name GENY Payment Terms L/C, T/T, D/P
Accuracy 0.1% and 0.2% Place of Origin CHINA
Model NO. YC98M Error ±0.1%
Model Number YC2000A Range 30-480V
Supply Ability 300/Year Certification ISO, CE
Power Supply External power supply Test lead power Accessories Included Optional

Product Description

High PrecisionPortable 3 Phase Portable Reference Standard for Single Phase Meter Calibration with 10-420V Voltage Range

Specifications:

The YC98M is a portable standard to verify active and reactive three phase meters (3 or 4 wires) and single phase meters. It is designed to work in the field to check the parameters of power line and test the meter.

 

Range 30-480V
Error ±0.1%
Harmonic 2nd -- 51st
Range (direct connection) 0.1A--10A
Range (clamp CT)

100A

5A,500A,1000A,2000A (option)

Error (direct connection) ±0.1%
Error (clamp CT)

±0.2% (5A, 100A)

±0.5% (other)

Harmonic 2nd -- 51st
Active power (direct connection) ±0.1%
Active power (clamp CT)

±0.2% (5A, 100A)

±0.5% (other)

Reactive power (direct connection) ±0.1%
Reactive power (clamp CT) ±0.5%
Active energy (direct connection) ±0.1%
Active energy (clamp CT)

±0.2% (5A, 100A)

±0.5% (other)

Reactive energy (direct connection) ±0.2%
Reactive energy (clamp CT) ±0.5%
Range 0º – 360º
Error ±0.1º
Range 45Hz – 65Hz
High frequency output(CH) --
Low frequency output(CL) 3600imp/kWh
Pulse ratio 1:1
Output level 5V
Input channel 1
Input level 5 -- 10V
Input frequency Max. 100Hz
Resolution 4.7”TFT color (480×272)
Vector diagram Yes
Waveform Yes
Energy accumulation Yes
CT ratio test Yes
Local parameter input Yes
Wiring emulation Yes
Self-calibration Yes
Recorder check Yes
Data storage Yes
Data storage qty 1000
External extend memory N/A
Screen printing N/A
Communication port RS232
Communication with PC Yes
Upload data Yes
External mini printer N/A
External keyboard N/A
Voltage Supply way External power; test lead power
Voltage Supply 45-480V, 50/60Hz
Ambient temperature -25°C -- +45°C
Relative humidity 40% -- 95%
Dimensions (W×H×D) (mm) 214×150×50
Weight (kg) 1.3kg

 

Description:

1. Current direct connection for high accuracy calibration

2. External connection clamp CT to extend the current test range

3. Plastic cover, safety and light

4. Internal large capacity rechargeable battery, suit for fieldwork

5. Small and light for carry

6. Select different clamp CT for different current test range

7. Self-calibration function

8. Wiring check function

9. Large color display screen

10. Screen copy function

11. Waveform display function

12. Vector diagram function

13. Energy accumulating

14. Input two pulse signal for master and slave meter synchronously calibration

15. Measurement data can be managed by computer via Rs232 interface

Applications:

1. Nation-level utility companies

2. Governmental bureaus of metrology

3. Big energy meter manufacturers

Primary Competitive Advantages:

1. High quality product

2. High stability

3. Friendly interface

4. Convenient operation